Mineral insulated cables
Heating Tape for Sensitive Surfaces
Application:
Heat tracing on apparatus, appliances and systems
Temperature maintenance on piping
Laboratory applications
Standard:
DIN VDE 0253
Voltage Rating:
230V
CABLE CONSTRUCTION:
Heating conductor
Insulation: Fluoropolymer.
Protective: Nickel-plated copper.
Outer sheath: E-glass textile.
Mechanical and Thermal Properties:
Maximum operating temperature: 260℃
Minimum installation temperature: -60℃
Minimum bending radius flat: 10 mm
Maximum output: 50 W/m
Approx Dimensions : 25 x 6 mm
Cable Parameter:
Heated length m | Nominal output W | ||
---|---|---|---|
Maximum temperature 100 °C | Maximum temperature 150 °C | Maximum temperature 200 °C | |
0.6 |
30 |
- |
- |
1.1 |
54 |
- |
- |
1.7 |
78 |
52 |
26 |
2.4 |
94 |
69 |
37 |
3.0 |
147 |
88 |
44 |
4.2 |
210 |
126 |
63 |
5.4 |
245 |
163 |
82 |
6.0 |
294 |
176 |
88 |
7.0 |
344 |
- |
- |
10.0 |
464 |
294 |
- |
12.5 |
623 |
371 |
192 |
15.0 |
705 |
441 |
220 |
17.5 |
864 |
521 |
- |
21.0 |
1008 |
611 |
315 |
28.0 |
1390 |
756 |
378 |